6. Talking diagnostics

Anchor example: examples/diagnostic_demo.rs — run it any time with cargo run --example diagnostic_demo.

In chapter 5 we moved a payload too big for one frame. Now we make the node say something a human cares about: what is wrong with it.

Picture a service technician plugging a laptop into a machine that quit in the field. The first two questions are always “what failed?” and “which box do I replace?” Diagnostics answers both. A faulting ECU broadcasts the codes that are active right now, keeps a history of ones that were active so a tool that arrives late still sees them, and exposes an identity so the tool knows exactly which unit and software it is talking to.

By the end of this chapter you will have built a fault code by hand, packed it into the active-fault message, read it back out, and you will know how the previously-active list, clearing, and identity fit around it.

What we are building

We work at the codec layer here — pure build-the-struct, encode, decode. No bus, no claim loop yet; just the bytes a diagnostic message is made of, so the anatomy is unmistakable. The example:

  1. builds a DTC (a single fault) from its three parts,
  2. packs two of them into a DM1 (the “active faults” message) with a lamp lit,
  3. encodes that to bytes and decodes it straight back, and
  4. round-trips a lone DTC field byte-for-byte.

Then we look at how the previously-active list, clearing, and identity ride the exact same types once you wrap a session around them.

Step 1 — the imports

#![allow(unused)]
fn main() {
{{#include ../../../examples/diagnostic_demo.rs:4:4}}
}

Five names, one module. Dtc is a single fault. Fmi says how it failed. DmDtcList is the message that carries a list of faults plus a lamp panel (DiagnosticLamps), and LampStatus is the state of one lamp. Everything lives under machbus::j1939 because ISOBUS diagnostics is the J1939 diagnostic layer with a few extra fields — see Diagnostics basics.

Step 2 — anatomy of a DTC

A Diagnostic Trouble Code is the unit of fault information, and it has exactly three meaningful parts:

PartFieldMeans
SPN — Suspect Parameter Numberspn: u32What is faulty (a numeric handle for the parameter or component). 19 bits on the wire.
FMI — Failure Mode Indicatorfmi: FmiHow it is faulty (VoltageLow, MechanicalFail, AbnormalRateChange, …). 5 bits.
Occurrence countoccurrence_count: u8How often it has happened. 7 bits.

Read together: “parameter X is failing in manner Y, and it has happened N times.” Build one and watch it survive a round-trip through its 4-byte wire form:

#![allow(unused)]
fn main() {
{{#include ../../../examples/diagnostic_demo.rs:48:61}}
}

The SPN here (0x1_2345) is wide on purpose: encoding clamps it to 19 bits and masks the count to 7 bits, so a Dtc always produces a valid wire field rather than corrupting the bytes around it. The assert_eq! proves the value you put in is the value you get back.

Step 3 — pack faults into a DM1

DM1 is the active diagnostics message: the faults a node has right now. In machbus it is DmDtcList — a lamp panel plus a Vec<Dtc>. We build one with the amber warning lamp on and two faults in the list:

#![allow(unused)]
fn main() {
{{#include ../../../examples/diagnostic_demo.rs:9:32}}
}

The lamp panel and the DTC list are independent fields. A DTC says what is wrong; the lamp says how loudly to alert the operator. We lit amber_warning and left the malfunction, red-stop, and engine-protect lamps at their default. The same two-byte lamp block rides at the front of every active/previously-active message, so a reader learns the codes and the alert level from one frame.

Step 4 — encode, send, decode

On a real bus you would put dm1.encode() on the wire and the receiver would call DmDtcList::decode(..). Here we do both ends in one breath so you can see the bytes survive the trip:

#![allow(unused)]
fn main() {
{{#include ../../../examples/diagnostic_demo.rs:34:46}}
}

encode always produces at least 8 bytes (lamps, then the DTCs), and decode returns the faults back as a Vec<Dtc>.

Step 5 — run it

cargo run --example diagnostic_demo

Expected output:

=== Diagnostic Demo ===
[DM1] 2 active DTCs, amber=On
[encode/decode] 10 bytes round-trip → 2 DTCs
  SPN=0x00208 FMI=VoltageLow OC=0
  SPN=0x000BE FMI=AbnormalRateChange OC=7

[DTC] 4-byte field: SPN=0x12345 → wire [45, 23, 27, 0C] → SPN=0x12345
✓ DTC round-trips byte-exact

What just happened

  Dtc{spn:520,  fmi:VoltageLow,         oc:0}  ─┐
  Dtc{spn:190,  fmi:AbnormalRateChange, oc:7}  ─┤
  lamps{ amber: On }                            ├─► DmDtcList.encode() ─► 10 bytes
                                                ─┘                          │
                                                                           ▼
        DmDtcList.decode(bytes)  ◄────────────────────────  back to 2 DTCs + lamps

Two faults plus a two-byte lamp block encoded to 10 bytes, and decoding gave back the same two faults. SPN 520 prints as 0x00208, SPN 190 as 0x000BE — that is just hex, not a different value. The standalone Dtc proved its 4-byte field round-trips byte-exact (45 23 27 0C), which is the guarantee everything above is built on.

Active vs previously-active

DM1 is only half of the read story. When a fault clears, it does not vanish — it moves to the previously-active list, which is published as DM2. DM2 uses the same DmDtcList type. The split is what lets a late-arriving service tool reconstruct what happened:

fault raised  ──►  ACTIVE list   ──► DM1  (broadcast, ~once a second)
                       │
                  fault clears / repaired
                       ▼
                  PREVIOUSLY-ACTIVE list ──► DM2  (sent on request)

A healthy node still broadcasts DM1 — with an empty list. “Nothing wrong” is a real, useful state, not the absence of a message.

Clearing and identity (the session surface)

The codec layer you just used has no list management on purpose. Once you wrap a session around it — plug in the Diagnostics plugin — the active/previous bookkeeping, the periodic DM1 broadcast, and request handling come for free. The shapes below are illustrative — for the verified behavior and the full plugin API, follow the Diagnostics tutorial.

#![allow(unused)]
fn main() {
// Illustrative shape, not a compiled call — see the tutorial.
ctrl.with_mut::<Diagnostics, _>(|diag| {
    diag.raise(Dtc { spn: 520, fmi: Fmi::VoltageLow, occurrence_count: 1 });
}); // adds an active fault → DM1
// ... after the repair ...
ctrl.with_mut::<Diagnostics, _>(|diag| {
    diag.clear();
}); // clears the active list
}

Clearing on the Diagnostics plugin is clear-all: clear() takes no arguments and empties the active DTC list in one call. (The DM protocol itself also defines a service-tool single clear that names one (spn, fmi) and gets an Ack or Nack back; that targeted form is not exposed on this plugin.)

Identity answers the second technician question — which box? A node can be asked for its identification strings (part number, serial, manufacturer, software version, and so on). The tool reads those to confirm exactly which ECU and firmware it is about to clear codes on or reflash. The codecs for those strings live alongside the DM messages; the tutorial covers them in full.

A note on size

Two faults fit in one CAN frame. A long fault list, or a multi-field identity string, will not — those payloads ride the transport protocol you met in chapter 5. You do not change how you build the message; the lower layer fragments and reassembles it for you.

Things that trip people up

  • No-fault is a valid state. An empty DmDtcList still encodes to a proper DM1. Do not treat “zero DTCs” as an error or a reason to stay silent.
  • Clearing is a move, not a delete. A cleared active code lands in the previously-active list. A technician an hour later still sees it on DM2. That is the whole point — do not expect it to disappear.
  • Occurrence counting is yours to manage at this layer. The count does not auto-increment. When the same (spn, fmi) recurs, bump the count instead of pushing a duplicate (use Dtc::matches, which compares by (spn, fmi) and ignores the count). The Diagnostics plugin’s raise is idempotent by (spn, fmi), so the counting policy stays explicitly yours.
  • Lamps and codes are independent. A lamp on with no code, or codes with all lamps off, are both legal. Decide your lamp policy deliberately; a reader will not infer one from the other.
  • Decoders are strict. A wrong length or a bad placeholder returns nothing rather than a half-parsed value. Check the result; do not unwrap blindly on bytes from the wire.

Validate locally

cargo run --example diagnostic_demo
make test

The example builds a DM1 with two DTCs, round-trips it through encode/decode, and asserts a single DTC field round-trips byte-exact. The test suite exercises every DM codec — round-trips, SPN clamping, lamp packing, and the strict-decode rejections.

What this proves / does not prove

Proves: you can build a DTC from its three parts, pack faults into the active message, and round-trip them through encode/decode in software — and you know where the previously-active list, clearing, and identity fit.

Does not prove: real-hardware timing, interoperability with a specific third-party ECU or service tool, or any conformance/certification claim. The same caveats from the earlier chapters apply.

Next

→ 7. Your first Virtual Terminal client — put a screen on the operator’s terminal.

See also

  • Diagnostics tutorial — the full DM family, the session diagnostics surface, clearing, memory access, and identity strings.
  • Diagnostics basics — the conceptual primer for DTCs and the DM messages.